The Box-Type Fixed AC Metal-Enclosed Switchgear is designed to be highly space-efficient, occupying only 50% of the volume of a conventional switchgear cabinet. This compact design makes it ideal choice for installations where space is limited, such as power plants, substations, industrial facilities, and high-rise buildings.
Switch cabinet technical parameters and component models
project | unit | parameter |
Rated voltage | KV | 3.6, 7.2,12 |
Rated power frequency withstand voltage | KV | To the ground, intersecting: 42; breaking: 48 |
Rated lightning impact withstand voltage | KV | To the ground, intersecting: 75: Break: 85 |
Rated frequency | Hz | 50 |
Rated current | A | 630,1250 |
Rated short circuit breaking current (risk value) | KA | 20, 25, 31.5 |
Rated short circuit closing current (peak value) | KA | 50,63,80 |
Rated dynamic stable current (peak value) | kA | 50, 63,80 |
Rated thermal stabilization current 4s (Rated value) | KA | 20,25,31.5 |
Protection level | IP2X | |
Dimensions (width × depth × height) | mm | 900×1000×2300 |
weight | kg | ≈600 |
Technical parameters of VS1-12 vacuum circuit breaker
project | unit | parameter |
Rated voltage | kv | 12 |
Rated current | A | 630,1250 |
Rated short circuit breaking current | kA | 20, 25,31.5 |
Rated short circuit closing current | kA | 50,63,80 |
Rated short-term withstand current (4s Rated value) | kA | 20, 25, 31.5 |
Rated peak withstand current (peak) | kA | 50,63,80 |
Mechanical life | Second-rate | 10000 |
Rated short circuit breaking current breaking times | Second-rate | 50 |
Rated operating sequence | Fen-0.3s-combination-180s-combination | |
Contact distance | mm | 11±1 |
Contact stroke | mm | 4±0.5 |
Interchange center distance | mm | 210 |
Opening speed | m/s | 1.2±0.2 |
Closed speed | m/s | 0.6±0.2 |
Opening time | ms | ≤60 |
Closed time | ms | ≤75 |
Three-phase opening simultaneous | ms | ≤2 |
Close the jump | ms | ≤2 |
Loop resistance | μΩ | ≤45 |
Cumulative wear thickness of contacts | mm | 3 |
Note: The technical parameters of other electrical components are found in their respective instructions. Solutions with a rated current of the switch cabinet greater than 1600A must be negotiated with the company. |